You have no items in your shopping cart.
TF832.3 240v Control Box
Technical Data
Operating Voltage | 220 / 240 V (-15... +10%) 50 Hz (50 - 60 Hz) |
---|---|
Fuse Rating | 10 A fast, 6 A slow |
Power Consumption | ca. 5 VA |
Max. load per output | |
terminal. 3 | 1.5A, cos ϕ 0.2 |
terminal. 4 | 4.0A, cos ϕ 0.4 |
terminal. 5 | 0.5A, cos ϕ 0.4 |
terminal. 6 | 0.5A, cos ϕ 0.4 |
terminal. 7 | 0.1A, cos ϕ 0.4 |
Total load | 5A, cos ϕ 0.4 |
Pre-purge time | ca 12 sec |
Pre-ignition time | ca 12 sec |
Post ignition time | ca 2-5 sec |
Delay time to Oil Valve 2 | 40 sec |
Lockout Safety Time | 10 sec |
Waiting time for malfunction remedy | None |
Reset time from Lockout | ca 90 sec |
Flame Detector | |
MZ 770 S | side-on and end-on viewing |
Light sensitivity MZ 770 S | > 6 Lux |
IRD 1010 | side-on or end-on viewing |
UVD 970 | end-on viewing |
Sensor operating current | min. 30 µA |
Weight incl. wiring base | 0.25 kg |
Mounting position | any |
Protection Class | IP 44 |
Recommended ambient operating temperature for control and flame detector | 0°C...+60°C |
approved and certified according to European standards | EN 230 |
Satronic TF832.3 240v Control Box
Oil Burner Safety Control
For 2-stage oil power burners up to 30kg/ h capacity and intermittent operations.
- Flame detection:
- Photoresistor MZ 770 S
- Infrared-flicker detector IRD 1010
- UV solid state sensor UVD 970
- Features
- 2 stage operation
- Post ignition time 2-5 sec
- Low voltage protection according to EN230
The TF 832.3 oil burner safety control boxes are suitable to control and monitor oil power burner up to 30 kg/h capacity (approved and certified according to EN230).
The TF 832.3 is fully compatible with the TF 730, 730-1 and TF 832. The flame detector IRD 911 must be replaced by its compatible type IRD 1010. An optional extension button (item no 70601) compensates for height differences.
Datasheets |
---|