SQN72.2A4A20BC 230v Servo Motor
Technical Data
Mains Voltage | AC 230 V –15 % +10 % |
---|---|
Mains Frequency | 50...60 Hz ± 6 % |
Drive Motor | Synchronous motor |
Power Consumption | 6 VA |
Angular Adjustment | Max. 160°, scale range 0...130° |
Mounting Position | Optional |
Degree of Protection | IP54 to DIN 40050, when using the cable entry gland provided plus plastic washers for the fixing screws M as shown under Dimensions. |
Safety Class | II to DIN EN 60730 |
Cable Entry | Rubber grommet for single cable with a max. jacket dia. of 11 mm. The hole in the grommet must be adequately matched to the dia. of the jacket. To ensure that the grommet will be tight, the cable must be correctly laid in this (no bends); the grommet is provided |
Cable Strain Relief | Cable strain relief with 2 fixing screws is provided |
Cable Connections | 2 plug-in spaces with connection terminals type CUM, made by Stelvio for the following types of connectors: - CUF 5-4 (plug-in space X1) - CUF 5-5 (plug-in space X2) Recommended cross-sectional area of stranded wire: min. 0.5 mm² , max. 1.5 mm² |
Ferrules | Adapted to cross-sectional area of stranded wire |
Direction of Rotation | Refer to «Type summary» |
Nominal and Holding Torque | Refer to «Type summary» |
Running Times | Refer to «Type summary» |
Lifecycle | Cycles (CLOSE > OPEN > CLOSE) with rated torque: typically 250.000 |
Weight (average) | Approx. 500 g |
On Time | 60%, max. 3 min. continuous operation |
Backlash between drive motor and drive shaft - As supplied - After 250,000 cycles |
≤1.2° ±,0.3° ≤1.5° ±,0.3° |
Siemens SQN72.2A4A20BC Servo Motor
230v
Electromotoric actuator for air dampers and control valves of oil or gas burners of small to medium capacity.
The SQN7... actuators are designed for driving gas or air dampers of oil or gas burners of small to medium capacity, for load-dependent control of the fuel and the combustion air volume:
• In connection with P-PI or PID controllers, such as the RWF40..., RWF5...
• Directly via the different types of burner controls, such as LOA..., LMO..., LME..., or LFL...
• In connection with 1- or 2-wire control or 3-position controllers
- Features
- Impact-proof and heat-resistant plastic housings
- Plug terminals for the electrical connections
- Maintenance-free gear train (can be disengaged)
- Internal position indication
- Easy-to-adjust end and auxiliary switches for setting the switching points
- Integrated electronic circuits
- Degree of protection IP54
• Holding torque: 0.7...1.3 Nm
• Running time: 4...30 s
• Direction of rotation: counterclockwise