01489 570737

MMI 810.1 Mod 43 240v Control Box

Excl. VAT: £231.76
Incl. VAT: £278.11
Brand: Satronic
Product Code: SAT25-019
Quantity:

Technical Data

Supply Voltage 220 / 240 V (-15... +10%)
50 Hz (50 - 60 Hz)
AC frequency variations result in proportional timing deviations
Fuse Rating max. 10 A rapid, 6 A slow
Power Consumption 10 VA
Max. Current per Output
term. 3 2A, cos ϕ 0.2
term. 4, B 2A, cos ϕ 0.4
term. 5, 6, C 1A, cos ϕ 0.4
Total load 5A, cos ϕ 0.4
Amplifier sensitivity 1 µA
Min. current from UV tube or ionisation probe 5 µA
Flame detector cable max. 20 m cable length
Waiting time for malfunction remedy None
Flame Detector
Ionisation Probe  
Infrared Flicker Detector IRD 1020
Weight incl. Base 350g
Mounting Position Any
Insulation Standard IP 44
Admissible ambient temperature for controller and flame detector -20° C… +60° C
Classified acc. to EN 298 BTLLXN

MMI 810.1 Mod 43 240v Control Box
Gas Burner Automatic Safety Control
For 2 stage force draught and combi oil/gas burners

  • Possible flame detectors:
  • Ionization probe
  • Infrared flicker detector

The gas burner automatic safety control MMI controls and monitors blown gas- and combined burners of any nominal thermal load (tested and certified according to EN 298).

The automatic safety controls MMI 810.1 models 13, 33 and 35 can also be utilized for burners on fixed hot air heaters (Direct air heaters according to DIN 4794).

Various types and model designations differentiate the automatic safety controls with respect to the programme times, as well as with regard to differing national standards.

MMI 810.1 Mod 43 Art. Nr. 0622520

MMI 810.1 Mod 43   Program Timing Seconds.
Waiting time at start ca. tw 9
Max. reaction time for air proving switch tlw 6
Pre-purge time tv1 40
Pre-ignition time tvz 3
T. ignition time tz 6
Safety time ts 3
Time delay term.6/term.C tv2 10

Datasheets

Follow us

Our Brands