IRD1020 Photocell C/W 1.8m Lead

Excl. VAT: £116.94
Incl. VAT: £140.33
Brand: Satronic
Product Code: SAT01-215
Quantity:

Technical Infomation

Supply Voltage 220 / 240 V (-15... +10%) 50 Hz (50 - 60 Hz)
Nominal Current Input approx. 4 mA
Power Consumption 1 VA
Ambient Temperature -20°C to +60°C
Insulation Standard IP 41
Mounting Attitude Any
Weight 40g
Flame viewing attitude side-on or end-on according to type
Spectral response 800 - 1100 nm
(with daylight filter) maximum 950 nm
Frequency range 15 Hz.... 250 Hz (-12 dB)
Sensitivity adjustment range approx. 1 : 20 (26 dB)
Switch-on delay (after connecting operating voltage) < 3.5 sec.
Response time < 0.1 sec.
Cut-out time < 1 sec.
Approved ambient parameter max. 95% at 30°C
- for operation -20° C... +60°C
- for storage -20° C... +80°C
Build-up of ice, penetration of water and condensing water are inadmissible  
Approvals according to European standards EN 298, as well as all other relevant Directives and standards

IRD1020 Photocell C/W 1.8m Lead
Infra-Red Flicker Detector
Flame monitoring device for Oil and Gas flames

  • Kit Contents
  • Satronic IRD 1020 Flicker Detector Photocell end on
  • Lead to suit

The IRD 1020.1 detector is used to supervise gas or oil flames. This flame monitoring device should be connected to a Satronic oil burner control box. Monitoring is based on the infra-red flicker principle, in other words, the flickering infra-red light of the flame is detected. The steady radiation from, for example, the glowing refractory layer on the inside of the boiler, has no effect on the detector. The IRD 1020.1 replaces the IRD 1020 and 920.

When exchanging the IRD 1020, care must be taken that the corresponding IRD 1020.1 with the same imprint (blue or white) is used (see page 3 and 4).

When exchanging the IRD 920, care must be taken to wire the sensor correctly (see page 3), and the existing holder must be exchanged with the magnetic holder M93. For replacement of the IRD 920 with IRD 1020.1 is the sensor cable also needed.

The infra-red flicker detector can be used with any one of the following control boxes:

  • DKG 972
  • DLG 974, 976
  • DMG 970, 971, 972, 973
  • TFI 812.2
  • MMI 810, 811, 812, 815, 816, 962
  • TMG 740-2, 740-3
  • SGU 930, 930i