View Catalogue  
Request Catalogue  

Multi-Jet Dry-Dial Meter for Warm Water

MULTI-JET PHOTO
MULTI-JET TABLE
  • Multi-jet dry-dial meter for warm water
  • Nominal flowrate Qn 1.5-15m3/h
  • EEC approval metrological Class B.H
  • ELSTER ConText® inscription system

 

MULTI-JET DIAGRAM A
MULTI JET DIAGRAM B
MULTI-JET DIAGRAM 3

 

MULTI JET METER M190MTHRMTHR-S
Meter Size / Normal Flow Rate Qn M3/h 1.5 2.5 3.5 6 10 15 15 1.5 2.5 6 10
Nominal Size DN mm 15 20 25 25 40 50 50 20 20 25 40
  DN inch ½ ¾ 1 1 2 2 ¾ ¾ 1
Dimensions    
D1 Meter conn. thread ISO 228 / 1 inch G ¾ B G 1 B G 1 ¼ B G 1 ¼ B G 2 B G 2 ½ B Flange G 1 B G 1 B G 1 ¼ B G 2 B
Conn. pipe thread ISO 7 / 1 inch R ½ R ¾ R 1 R 1 R 1½ R 2 - R ¾ R ¾ R ¾ R 1 ½
L1 Meter Length   mm 165 190 260 260 300 270 270 105 105 150 200
Connector Length   mm 40 50 60 60 70 60 - 50 50 60 70
B1 Width   mm 100 100 100 100 100 100 100 100 100 100 100
B2 Distance Pipe Axis to meter axis   mm - - - - - - - 80 80 94 120
H1 Centerline Height   mm 31 31 43 43 46 46 68 - - - -
H2 Overall Height   mm 115 115 130 130 153 153 160 135 135 151 195
Weight   kg 1.5 1.6 2.5 2.5 3.7 4.5 8.5 1.8 1.8 2.6 5.5
Performance Characteristics    
Maximum Flow Rate Q max m3/h 3 5 7 12 20 30 30 3 5 12 20
Transitional Flow Rate Q1 l/h 120 200 200 480 800 1500 1500 120 200 480 800
Minimum Flow Rate Qmin l/h 25 35 35 80 150 200 200 25 35 80 150
Starting Flow ** l/h 10 15 15 50 50 100 100 10 15 30 50
Continuous Load

1.6 x Q

(approx)

l/h 2500 4000 5600 10000 16000 25000 25000 2500 400 10000 25000
Temperature Tmax °C 90 90 90 90 90 90 90 90 90 90 90
Pressure Rating PN bar 16 16 16 16 16 16 16 16 16 16 16
Row Capacity at 1 bar pressure lost m3/h 4.4 6.7 7.2 12.8 22 32 32 4.0 6.7 7.2 7.2  

 