Technical Information

Operating Voltage 220 / 240 V (-15... +10%)
50 Hz (±5%)
Fuse Rating 10 A fast, 6 A slow
Power Consumption ca. 12 VA
Max. Load per Output
- term. 3 ignition trafo 1.5 A, cos ϕ 0.2
- term. 4 motor 2.0 A, cos ϕ 0.4
- term. 5 + 6 solenoid valves 1.0 A, cos ϕ 0.4
- term. B alarm indicator 1,0 A, cos ϕ 0.4
Total load 5.0 A, cos ϕ 0.4
max. 20 A during 0,5 sec

Direct lockout after a loss of flame during operation

Satronic DMG 970 Mod 03 230v Control Box
Gas Burner Safety Control
For 2 stage forced draught and combination oil & gas burners.

  • Possible Flame Detectors
  • Ionisation probe
  • Infrared flicker detector 1020
  • UV flame sensor UVD 971

The burner control box DMG 970 controls and supervises power burner for gas and dual fuel. The control box is approved and certified according the relevant European standards. The use on direct air heaters according DIN 4794 is also possible.

The microprocessor- based programming sequence ensures extremely stable timings independent of voltage variations, ambient temperature and/or switch-on cycles. The built-in information system not only provides a continuous monitoring of the actual state of the box (very helpful especially for monitoring the start-up phase) but also informs about the cause of a possible lock out. The lock out cause is stored in such a way that it can be retrieved even after a power failure.

The control box is designed for maximum safety in case of fluctuations in the voltage supply. If the mains voltage drops below the permitted level, operation is interrupted and the control box automatically prevents the start sequence from being repeated. In this way, the safety of the system is not put at risk by a drop in the mains voltage. This low-voltage protection works not only during start-up but also permanently during operation.

DMG 970 Mod 03   Timing (Sec)
Waiting time start   0
Max. reaction time for air proving switch tlw 60
Supervised pre-purge time tv1 40
Pre-ignition time tvz 3
Ignition time total tz 5.5
Stray light monitoring tf 5
Safety time ts 3
Delay 2nd stage tv2 12.5