MC 9500 Dosing Pumps
PULSAtrol MC9500 Series include as standard, four tagable timers two water meter totalisers user configured as dry contact or hall effect, dry contact alarm relay and alarm output relay. Options include two 4-20 mA outputs, conduit connection for power and relays, communications, language and agency approvals.
All 9500 Series include as standard, four tagable timers, two water meter totalisers user configured as dry contact or hall effect, four drum level inputs, dry contact alarm relay and alarm output relay. Options include up to four 4-20 mA inputs and outputs, conduit connection for power and relays, communications, language and agency approvals.
Features
- Up to four user selectable timers that will operate in any one of seven modes
- Manually entered data collection field with ten user defined fields and units - stored in the controller's history (downloadable with PULSAworks software)
- Four single-point drum level inputs (9500 only)
- Multiple security levels and lockable input window
- One or two point calibration
- Ability to reset relay "ON" times with date/time stamp
- Calibration date/time stamp
- Two water meter input capability (dry contact or hall effect)
- Alarm powered & dry contact relays
- Optional 4-20mA input (9500 only) and output capability
- Alarm LED - relay or optional callback status
- Self charging capacitor to maintain time and history for up to two weeks in the event of a power loss to controller
- EEPROM protection of operating parameters during extended power outages
- Relay- drum level alarm - general alarm - flow alarm and power status LED's
- DIN connections for conductivity sensor and I/O
- Prewired incoming power and relay output connections on specified models (receptacle cords)
- Modular flow assembly with flow switch quick release sensors and sample port mounted on the polyethylene panel
- Optional remote communications capability via direct serial line or modem connection
General Specifications
Enclosures | NEMA 4X |
---|---|
Flow Switch Pressure | 125 psi / 8.6 bar |
Flow Switch Temperature | 125⁰F / 52⁰C Max |
Conductivity Range | 0-500 μS/cm, 0-2000 μS/cm, 0-5000 μS/cm, 0-10000 μS/cm, 0-20000 μS/cm |
ORP Range | 0-1000 mV |
Power Input | 90-250 VAC - 50/60 HZ - 100 VA |
Controller Display | Lighted Display 8 Line 64 x 128 pixel |
Timers | Programmable: Up to 4 operate in any one of seven modes |
Outputs | 6 Output Relays Powered: NO/NC (One Alarm), MC9500: (4) 4/20mA, MC9300: (2) 4/20mA |
Alarm Dry Contact | 2 - NO/NO |
Inputs | MC9500: (4) 4/20mA |
Drum Switch Inputs | MC9500: 4 Drum Level Inputs |
Water Meter Inputs | 2 Dry Contact or Hall Effect |
10 Bit A-D Resolution | Standard |
Front Panel HOA Control | Standard |
Recessed Front Panel Power Switch | Standard |
Lockable Viewing Window | Standard |
Average Current Draw | Line Voltage at 600 VA Per Relay, 120 VAC: Amps - 5 |
Controls | Conductivity, Conductivity and pH, Conductivity and ORP, Conductivity with Makeup / pH and ORP, Makeup Conductivity and pH Control, Dual Conductivity for use on open loop and closed loop or dual cooling tower systems, Communications - Optional, 4-20 mA Inputs and Outputs - Optional, pH Settings / Single or Dual Set Point- Optional |
Product Options |
|
Accessories | Corrosion Coupon Racks Metering Pumps Motorized Ball Valves Solenoids Water Meters |
Sensor Specifications
Sensor Temperature | 125⁰F / 52⁰C Max |
---|---|
Sensor Pressure | 125 psi / 8.6 bar |