The electro-thermal link is for installing in a position where a fire hazard may occur, e.g. above a burner of an air heater or boiler. The fire will melt the fusible metal link and interrupt the electrical supply to either a gas valve or alarm etc. The link consists of a purpose built steel box with a perforated cover having a temperature sensitive fuse. The unit should be mounted so that the perforated cover faces downwards and ventilation holes in the sides must not be obstructed.
Technical Specification
The link is electrically rated at 5 amps maximum on 200/250 V, single phase, 50 Hz and melts at 155 °F (68°C). Dimensions : 75 mm length x 50 mm width x 30 mm depth complete with 20 mm conduit entry in one end.